Aluminium Solar Mounting StructureSolar MMS DesignFinite Element AnalysisIS 8147IS 875 Part 3IS 1893Wind Load AnalysisBuckling AnalysisAluminium ExtrusionANSYS Mechanical

Aluminium Solar Mounting Structure FEA: Hybrid Aluminium and Steel Design to IS 8147

ANSYS FEA of an extruded aluminium solar mounting structure on galvanised steel posts, checked for wind and seismic loads to IS 8147, IS 800 and IS 875.

All Case Studies
Aluminium Solar Mounting Structure FEA: Hybrid Aluminium and Steel Design to IS 8147 — featured
Context

Project brief

An aluminium extrusion producer wanted to offer its solar developer customers an aluminium solar mounting structure in place of the usual all-steel table. Aluminium does not rust and is light to handle on site, but it is much less stiff than steel and it is designed to a different code. Before the developer would let it go on a live plant, the producer needed a structure that was properly engineered, analysed and documented.

Shirsh Technosolutions designed and analysed the structure. We developed a hybrid layout with extruded 6005 aluminium rafters, purlins and bracings carried on hot-dip galvanised steel posts, then verified the full table by finite element analysis in ANSYS for dead, wind and seismic loads to IS 8147, IS 800, IS 801, IS 875 Part 3 and IS 1893. The package went out with the analysis report, GA and part drawings and a section-wise bill of quantities.

The problem

What was at risk

A solar mounting structure in aluminium is not a straight swap of material. The lower elastic modulus means deflection, not strength, often decides the section, and thin-walled extrusions can buckle before they yield. The developer also had its own fixed points. The posts had to be the same galvanised steel section already used across the plant so the piles and site marking would not change, and the post spacing had to match the existing rows.

Joining aluminium to steel brings its own questions. Galvanic corrosion at every rafter-to-post and bracing joint had to be handled, and the alloy had to be one the producer could actually extrude. The developer's engineering team reviewed the first design in detail and asked for changes to material data, load combinations, deflection limits and the support reactions needed for the pile check.

Our answer

Solution offered

Concept first, then the hybrid. An earlier concept study in aluminium had already shown a worthwhile weight saving when the delta frame was replaced by a Y-shaped frame. For the plant design we moved to a hybrid: steel posts to suit the existing foundations, and aluminium for everything above. When the first alloy proposed could not be extruded at the plant, we recommended 6005, which was adopted.

A 3D solid model of the whole table. The full two-row table was modelled in ANSYS Mechanical with every post, rafter, purlin, bracing, connector, cleat and purlin coupler as a solid body. Modules were represented as stiff mass panels so wind pressure reached the purlins without the glass adding stiffness. Bonded contact was used where parts are fixed together and no-separation contact at the bolted joints.

Loads to the Indian codes. Wind pressure on the module plane was worked out to IS 875 Part 3 for both uplift and downward wind, plus wind on the exposed member faces for the side case. Seismic loads followed IS 1893 in both horizontal directions. Five service combinations were run: dead load with uplift, downward and side wind, and dead load with seismic in each direction.

Each material checked to its own code. Steel parts were checked to IS 800 working stress design and IS 801 for the light gauge section, and aluminium members to IS 8147 with allowable stress derived from the proof stress. Deflection limits came from IS 800 Table 6, with separate limits for the post, the cantilever rafter and the purlins.

Stability and foundations covered. An eigenvalue buckling analysis confirmed the load factor against bifurcation buckling was well above the minimum design factor. Post base reactions, forces and moments, were tabulated for every load case so the developer could verify its pile design.

Review comments closed out. The developer's review points were worked into the revised model: the correct post steel grade, the post deflection limit, both seismic directions and the base reactions. For the aluminium-to-steel joints we recommended anodising to IS 1868 with an anti-oxidant compound at the contact faces to keep galvanic corrosion in check.

Common questions

Which code is used to design an aluminium solar mounting structure in India? Aluminium members are designed to IS 8147, the Indian code for aluminium alloys in structures, with allowable stresses taken from the alloy's proof stress. Wind loads come from IS 875 Part 3 and seismic loads from IS 1893, while any steel parts such as posts and connectors are checked to IS 800 and IS 801.

Can aluminium and galvanised steel be used together in a solar structure? Yes, and it is a practical choice when the existing piles and posts are steel. The joints need care: anodised aluminium, a suitable coating or isolating compound at the contact faces, and stainless fasteners keep galvanic corrosion under control. The analysis then has to treat each material with its own stiffness and allowable stress.

The hurdles

Challenges we overcame

Aluminium is far less stiff than steel, so deflection drives the sections

Thin extruded members that can buckle before they yield

Steel posts fixed by the existing piles and row spacing

Galvanic corrosion at every aluminium-to-steel joint

An alloy that could actually be extruded at the producer's plant

A detailed design review by the developer's engineers

Methodology

How we executed

  1. 1

    Took the module data, post section, pile details and site design data

  2. 2

    Developed the hybrid layout with aluminium members on galvanised steel posts

  3. 3

    Built a solid 3D model of the full table in ANSYS Mechanical

  4. 4

    Worked out wind loads to IS 875 Part 3 and seismic loads to IS 1893

  5. 5

    Ran uplift, downward and side wind and two seismic combinations

  6. 6

    Checked steel to IS 800 and IS 801 and aluminium to IS 8147

  7. 7

    Ran eigenvalue buckling and tabulated post base reactions

  8. 8

    Closed the developer's review comments and issued report, drawings and BOQ

Results

Project outcome

Every member stayed within its code allowable stress in all five load cases.

Post, rafter and purlin deflections came out within the IS 800 Table 6 limits.

Buckling load factor well above the minimum design factor.

Post base reactions supplied for the developer's pile check.

Full package issued: analysis report, GA and part drawings and section-wise BOQ.

Visuals

Project gallery

Read more

Related insights

Article

An Eigenvalue Is Not a Capacity: Reading FEA Buckling Results

An eigenvalue load factor of 3 can look like a safe margin, yet on a thin cylinder it may sit close to the real lower bound. I set out what a linear buckling analysis can claim, how EN 1993-1-6 builds imperfections back in, and what I ask to see in a buckling report.

Read
Article

Four Quiet Ways the IS 875 Wind Load Goes Wrong on a Solar Array

The wind-load calculation almost never fails an audit. It fails the structure. IS 875 (Part 3) is a sound loading code, and the arithmetic in most reports is right. What moves the answer is a handful of small choices in how the code gets applied, and on a light tilted array those small moves decide which members are under-built. Here is the chain done properly, and the four places it usually slips.

Read
Article

How to Check a Cold-Formed Solar Mounting Structure to IS 801: A Step-by-Step Guide

Most ground-mounted solar structures in India are made from cold-formed steel: thin steel sheet bent into channels and hat sections. Engineers find the wind load from IS 875 Part 3, then check the steel using IS 801. Two mistakes are very common. First, engineers use the full cross-section, but thin steel does not work that way: part of it buckles early, so the code makes you use only the "effective" part. Second, engineers check only the steady (static) load and skip the moving (dynamic) effects. This guide explains both problems in simple steps. It then checks the four main members of a solar structure: post, rafter, bracing, and a 1 mm hat purlin: with full numbers, so you can see exactly where the common shortcuts go wrong.